Passive fire protection compartmentation surveys are not a blanket across all buildings. Buildings have different types and usages, so compartmentation will have different requirements.
If you are not sure of the type of compartmentation survey you need, we have put this guide together for you. Or you can just get in touch with us, and we can help you.
Why Building Type Matters in PFP Compartmentation Surveys
Building type dictates how a structure is compartmentalised, the types of fire-stopping materials required, and its specific statutory obligations under UK fire safety legislation.
A PFP compartmentation survey must be tailored to the exact building type.
Residential Buildings
PFP compartmentation surveys help landlords, managing agents and responsible persons comply with regulations like the Fire Safety Act 2021 and the Building Safety Act 2022.
Each flat is meant to act as its own fire-resisting box, which is what supports the stay-put strategy used in most blocks. The survey checks that this is actually holding up.
Typically Applies to:
Apartment blocks of all sizes
Purpose-built blocks of flats, where the 11m and 18m height thresholds affect classification
Converted properties, where the original layout was never designed for multi-occupancy
HMOs, which often have the worst gaps due to repeated layout changes
Mixed-use blocks, where separation between commercial and residential use is a common failure point
What the survey checks, and what it commonly finds:
Compartment walls and floors between flats and between flats and common parts, often breached by unsealed pipework or cabling
Flat entrance doors, checking closing action, intumescent strips and frame gaps, which frequently turn out missing or perished
Cavity barriers in roof voids and lofts, which are often missing entirely above multiple flats
Riser cupboards and service ducts are prone to unsealed builders' work openings.
Breaches left by later works, such as rewiring, satellite installs or kitchen extensions
Access is rarely full coverage. Surveyors typically sample flats when vacant or during other works, and the report states clearly what was and wasn't accessed.
Commercial Buildings
PFP compartmentation surveys help building owners and occupiers comply with the Regulatory Reform (Fire Safety) Order 2005, and the Building Safety Act 2022, where relevant. Commercial buildings change tenants often, and every fit-out is a chance for compartmentation to be breached.
Typically Applies to:
Multi-tenanted office buildings, where each tenant's space needs to be sealed from the next and from shared risers
Retail units and shopping centres, where the separation between units and back-of-house areas is a common weak point
Warehouses and logistics units, where plant rooms and mezzanine levels still need fire-rated separation
Mixed commercial estates sharing risers, ceiling voids or service routes
What the survey checks, and what it commonly finds:
Breaches in walls and floors between tenants, and between tenants and common parts
Suspended ceiling voids, where cabling and IT installs often breach fire-rated ceilings without resealing
Riser shafts and service ducts are frequently found with gaps around pipework or cable trays
Escape route doors and partitions, sometimes wedged open or fitted with non-compliant hold-open devices
Fire stopping removed or never reinstated after Cat A or Cat B fit-outs
Access to common areas and risers is usually straightforward, but access to each tenant's actual space is often limited, and fit-outs can introduce breaches the landlord never sees. The report records which areas were inspected and flags any that weren't.
Industrial Buildings
PFP compartmentation surveys help owners and operators comply with the Regulatory Reform (Fire Safety) Order 2005 and relevant building regulations. Industrial buildings often hold high fire loads, and large open floor plates let fire travel fast once it gets past a compartment line.
Typically Applies to:
Manufacturing facilities, where process areas sit next to offices or storage
Warehouses and distribution centres, where large open spans make fire spread fast
Cold storage and food production sites, where insulated panel construction brings its own fire-stopping challenges
Mixed industrial estates with shared boundary walls between units
What the survey checks, and what it commonly finds:
Party walls and floors between units, often gapped where insulated panels meet
Cavity barriers in roof voids and above suspended ceilings are sometimes missing or displaced
Fire stopping around conveyors, ductwork and pipe runs, prone to degrading from movement or vibration
Loading bay shutters and openings are sometimes missing proper fire-rated seals
Compartment walls that stop at the roof deck instead of being sealed to it
Access is usually easier than residential or multi-tenant commercial sites, since one occupier typically controls the whole unit. Live production areas, racking and stored goods can still block sightlines to walls and roof voids, and the report notes any areas that couldn't be fully inspected.
Healthcare Buildings
Healthcare building PFP compartmentation surveys help NHS trusts and private providers comply with HTM 05-02 and the Regulatory Reform (Fire Safety) Order 2005. Hospitals rely on progressive horizontal evacuation, moving patients sideways into an adjacent compartment rather than out of the building. That only works if the compartment lines are intact.
Typically Applies to:
Acute hospitals, where compartmentation supports horizontal evacuation between wards
Care homes, where most residents cannot evacuate quickly or at all
Mental health facilities, where door hardware and compartmentation need to balance fire safety with ligature resistance
GP surgeries and outpatient clinics, smaller in scale but still subject to the same Firecode principles
What the survey checks, and what it commonly finds:
Compartment and subcompartment walls between wards and departments, often breached around medical gas pipework
Fire doors and their self-closers, sometimes propped open for trolley or bed access
Smoke doors, which can fail to close fully due to flooring changes or clutter
Riser cupboards and ducted services are prone to unsealed penetrations from cabling and equipment installs
Cavity barriers above operating departments and critical care areas
Access to healthcare sites is tightly controlled. Clinical areas can't be disrupted, and some spaces need infection control measures or staff escort before a surveyor can enter. Surveys are usually phased around clinical activity, and the report notes where access was restricted.
Educational Buildings
Educational building PFP compartmentation surveys help schools, colleges and universities comply with the Regulatory Reform (Fire Safety) Order 2005 and the Department for Education's Building Bulletin 100 guidance.
Most education buildings evacuate everyone at once rather than relying on stay-put, but compartmentation still limits how fast a fire spreads while that happens.
Typically Applies to:
Primary and secondary schools are often built and extended in phases over decades.
Further education colleges, which mix classrooms with workshops and specialist labs
University buildings, ranging from lecture halls to halls of residence that behave more like residential blocks
Mixed campus sites with multiple buildings of different ages and construction types
What the survey checks, and what it commonly finds:
Compartment walls between classroom blocks, wings and phases of construction
Walls and doors around assembly halls, gyms and dining areas
Riser cupboards and ceiling voids, frequently breached by data cabling for classroom IT
Boiler rooms, kitchens and plant areas, which need clear separation from teaching spaces
Breaches left by retrofitted extensions, disabled access works or building alterations
Access is usually good outside term time, when surveys can be intrusive without disrupting teaching. During term time, live classrooms and timetabling limit what can be inspected. Older buildings built in separate phases often mix different compartmentation standards, which the report should flag clearly.
Hospitality Buildings
PFP compartmentation surveys help hotels, pubs and restaurants comply with the Regulatory Reform (Fire Safety) Order 2005.
Typically Applies to:
Hotels, where each guest room functions as its own compartment, similar to a flat
Serviced apartments, which combine hotel-style operation with longer stays
Pubs and bars with overnight accommodation above
Restaurants and conference or banqueting venues, where commercial kitchens add their own risks
What the survey checks, and what it commonly finds
Guest room doors and their self-closers, which housekeeping sometimes disables for convenience
Walls and floors between guest rooms and corridors
Fire stopping around the kitchen extraction ductwork is a high-risk area in any commercial kitchen
Riser cupboards and plant rooms
Breaches from frequent refurbishment cycles, common in hotels that update rooms regularly
Separation between the function or conference rooms and the guest accommodation
Access is usually straightforward, since most of the building is under one operator's control. Live guest occupancy still limits room-by-room inspection during operation, so surveys often need to work around occupancy levels and coordinate with housekeeping.
What the PFP Compartmentation Report Delivers
Every PFP compartmentation survey from GRJ Surveying ends with a clear, actionable report. This applies regardless of building type.
A prioritised remedial schedule, organised by severity and risk rather than a flat list of defects
Photographic evidence for each defect, linked to its exact location
A clear statement of survey coverage and limitations, including which areas were and weren't accessed
Reference to the fire rating required at each location, so remedial works can be specified correctly
A format suitable for your compliance records.
This gives you one consistent standard of reporting. It holds across all types of buildings, no matter how different the access challenges or defects are on site.
Why Every Building Type Needs a Compartmentation Survey
PFP compartmentation only works if it's still intact. A compartment wall that passed inspection on day one can be breached by the next contractor who drills through it. That's true whether the building is a block of flats, an office, a warehouse, a hospital, a school or a hotel.
The building type changes what a surveyor looks for and how access works. It doesn't change the underlying risk. Every penetration, every fire door and every cavity barrier is doing a specific job, and a PFP compartmentation survey is the only way to confirm that the job is still being done.
If you're a responsible person, a facilities manager or a building owner, a survey gives you something a general fire risk assessment can't. It tells you exactly where your compartmentation stands today, not where it stood when the building was built.